Search Results (806 CVEs found)

CVE Vendors Products Updated CVSS v3.1
CVE-2020-7564 1 Schneider-electric 40 Modicon M340 Bmx Noc 0401, Modicon M340 Bmx Noc 0401 Firmware, Modicon M340 Bmx Noe 0100 and 37 more 2026-05-29 6.3 Medium
A CWE-120: Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') vulnerability exists in the Web Server on Modicon M340, Modicon Quantum and Modicon Premium Legacy offers and their Communication Modules (see notification for details) which could cause write access and the execution of commands when uploading a specially crafted file on the controller over FTP.
CVE-2020-7563 1 Schneider-electric 40 Modicon M340 Bmx Noc 0401, Modicon M340 Bmx Noc 0401 Firmware, Modicon M340 Bmx Noe 0100 and 37 more 2026-05-29 6.3 Medium
A CWE-787: Out-of-bounds Write vulnerability exists in the Web Server on Modicon M340, Modicon Quantum and Modicon Premium Legacy offers and their Communication Modules (see notification for details) which could cause corruption of data, a crash, or code execution when uploading a specially crafted file on the controller over FTP.
CVE-2020-7562 1 Schneider-electric 40 Modicon M340 Bmx Noc 0401, Modicon M340 Bmx Noc 0401 Firmware, Modicon M340 Bmx Noe 0100 and 37 more 2026-05-29 6.3 Medium
A CWE-125: Out-of-Bounds Read vulnerability exists in the Web Server on Modicon M340, Modicon Quantum and Modicon Premium Legacy offers and their Communication Modules (see notification for details) which could cause a segmentation fault or a buffer overflow when uploading a specially crafted file on the controller over FTP.
CVE-2017-7575 1 Schneider-electric 2 Modicon Tm221ce16r, Modicon Tm221ce16r Firmware 2026-05-29 9.8 Critical
Schneider Electric Modicon TM221CE16R 1.3.3.3 devices allow remote attackers to discover the application-protection password via a \x00\x01\x00\x00\x00\x05\x01\x5a\x00\x03\x00 request to the Modbus port (502/tcp). Subsequently the application may be arbitrarily downloaded, modified, and uploaded.
CVE-2017-7574 1 Schneider-electric 3 Modicon Tm221ce16r, Modicon Tm221ce16r Firmware, Somachine 2026-05-29 10 Critical
Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a password. This XML file is AES-CBC encrypted; however, the key used for encryption (SoMachineBasicSoMachineBasicSoMa) cannot be changed. After decrypting the XML file with this key, the user password can be found in the decrypted data. After reading the user password, the project can be opened and modified with the Schneider product.
CVE-2017-6030 1 Schneider-electric 6 Modicon M221, Modicon M221 Firmware, Modicon M241 and 3 more 2026-05-29 6.5 Medium
A Predictable Value Range from Previous Values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial sequence numbers that may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections.
CVE-2018-7798 1 Schneider-electric 2 Modicon M221, Somachine Basic 2026-05-29 8.2 High
A Insufficient Verification of Data Authenticity (CWE-345) vulnerability exists in the Modicon M221, all versions, which could cause a change of IPv4 configuration (IP address, mask and gateway) when remotely connected to the device.
CVE-2022-0715 1 Schneider-electric 66 Scl Series 1029 Ups, Scl Series 1029 Ups Firmware, Scl Series 1030 Ups and 63 more 2026-05-29 8.9 High
A CWE-287: Improper Authentication vulnerability exists that could cause an attacker to arbitrarily change the behavior of the UPS when a key is leaked and used to upload malicious firmware. Affected Product: APC Smart-UPS Family: SMT Series (SMT Series ID=18: UPS 09.8 and prior / SMT Series ID=1040: UPS 01.2 and prior / SMT Series ID=1031: UPS 03.1 and prior), SMC Series (SMC Series ID=1005: UPS 14.1 and prior / SMC Series ID=1007: UPS 11.0 and prior / SMC Series ID=1041: UPS 01.1 and prior), SCL Series (SCL Series ID=1030: UPS 02.5 and prior / SCL Series ID=1036: UPS 02.5 and prior), SMX Series (SMX Series ID=20: UPS 10.2 and prior / SMX Series ID=23: UPS 07.0 and prior), SRT Series (SRT Series ID=1010/1019/1025: UPS 08.3 and prior / SRT Series ID=1024: UPS 01.0 and prior / SRT Series ID=1020: UPS 10.4 and prior / SRT Series ID=1021: UPS 12.2 and prior / SRT Series ID=1001/1013: UPS 05.1 and prior / SRT Series ID=1002/1014: UPSa05.2 and prior), APC SmartConnect Family: SMT Series (SMT Series ID=1015: UPS 04.5 and prior), SMC Series (SMC Series ID=1018: UPS 04.2 and prior), SMTL Series (SMTL Series ID=1026: UPS 02.9 and prior), SCL Series (SCL Series ID=1029: UPS 02.5 and prior / SCL Series ID=1030: UPS 02.5 and prior / SCL Series ID=1036: UPS 02.5 and prior / SCL Series ID=1037: UPS 03.1 and prior), SMX Series (SMX Series ID=1031: UPS 03.1 and prior)
CVE-2018-7794 1 Schneider-electric 58 140cpu65150, 140cpu65150 Firmware, 140cpu65160 and 55 more 2026-05-29 7.5 High
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Modicon Quantum, Modicon Premium (see security notification for specific versions) which could cause a Denial of Service when reading data with invalid index using Modbus TCP.
CVE-2018-7792 1 Schneider-electric 2 Modicon M221, Modicon M221 Firmware 2026-05-29 7.5 High
A Permissions, Privileges, and Access Control vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to decode the password using rainbow table.
CVE-2021-22792 1 Schneider-electric 49 Modicon M340 Bmxp341000, Modicon M340 Bmxp342010, Modicon M340 Bmxp342020 and 46 more 2026-05-29 6.5 Medium
A CWE-476: NULL Pointer Dereference vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all Unity Pro versions (former name of EcoStruxureª Control Expert, all versions), PLC Simulator for EcoStruxureª Process Expert including all HDCS versions (former name of EcoStruxureª Process Expert, all versions), Modicon Quantum CPU (part numbers 140CPU*, all versions), Modicon Premium CPU (part numbers TSXP5*, all versions).
CVE-2018-7791 1 Schneider-electric 2 Modicon M221, Modicon M221 Firmware 2026-05-29 9.8 Critical
A Permissions, Privileges, and Access Control vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to overwrite the original password with their password. If an attacker exploits this vulnerability and overwrite the password, the attacker can upload the original program from the PLC.
CVE-2021-22790 1 Schneider-electric 49 Modicon M340 Bmxp341000, Modicon M340 Bmxp342010, Modicon M340 Bmxp342020 and 46 more 2026-05-29 6.5 Medium
A CWE-125: Out-of-bounds Read vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all Unity Pro versions (former name of EcoStruxureª Control Expert, all versions), PLC Simulator for EcoStruxureª Process Expert including all HDCS versions (former name of EcoStruxureª Process Expert, all versions), Modicon Quantum CPU (part numbers 140CPU*, all versions), Modicon Premium CPU (part numbers TSXP5*, all versions).
CVE-2018-7790 1 Schneider-electric 2 Modicon M221, Modicon M221 Firmware 2026-05-29 9.8 Critical
An Information Management Error vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to replay authentication sequences. If an attacker exploits this vulnerability and connects to a Modicon M221, the attacker can upload the original program from the PLC.
CVE-2021-22779 1 Schneider-electric 61 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 58 more 2026-05-29 6.5 Medium
Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller.
CVE-2021-22768 1 Schneider-electric 4 Powerlogic Egx100, Powerlogic Egx100 Firmware, Powerlogic Egx300 and 1 more 2026-05-29 9.8 Critical
A CWE-20: Improper Input Validation vulnerability exists in PowerLogic EGX100 (Versions 3.0.0 and newer) and PowerLogic EGX300 (All Versions) that could cause denial of service or remote code execution via a specially crafted HTTP packet.This CVE ID is unique from CVE-2021-22767
CVE-2018-7789 1 Schneider-electric 2 Modicon M221, Modicon M221 Firmware 2026-05-29 4.8 Medium
An Improper Check for Unusual or Exceptional Conditions vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to remotely reboot Modicon M221 using crafted programing protocol frames.
CVE-2021-22765 1 Schneider-electric 4 Powerlogic Egx100, Powerlogic Egx100 Firmware, Powerlogic Egx300 and 1 more 2026-05-29 9.8 Critical
A CWE-20: Improper Input Validation vulnerability exists in PowerLogic EGX100 (Versions 3.0.0 and newer) and PowerLogic EGX300 (All Versions) that could cause denial of service or remote code execution via a specially crafted HTTP packet
CVE-2020-7549 1 Schneider-electric 38 140cpu65150, 140cpu65150 Firmware, 140noc78000 and 35 more 2026-05-28 7.5 High
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause denial of HTTP and FTP services when a series of specially crafted requests is sent to the controller over HTTP.
CVE-2020-7489 1 Schneider-electric 8 Ecostruxure Machine Expert, Modicon M100, Modicon M100 Firmware and 5 more 2026-05-28 9.8 Critical
A CWE-74: Improper Neutralization of Special Elements in Output Used by a Downstream Component ('Injection') vulnerability exists on EcoStruxure Machine Expert – Basic or SoMachine Basic programming software (versions in security notification). The result of this vulnerability, DLL substitution, could allow the transference of malicious code to the controller.