Search Results (2276 CVEs found)

CVE Vendors Products Updated CVSS v3.1
CVE-2017-2680 1 Siemens 183 S110 Pn, Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware and 180 more 2025-04-20 6.5 Medium
Specially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected.
CVE-2015-7705 4 Citrix, Netapp, Ntp and 1 more 10 Xenserver, Clustered Data Ontap, Data Ontap and 7 more 2025-04-20 9.8 Critical
The rate limiting feature in NTP 4.x before 4.2.8p4 and 4.3.x before 4.3.77 allows remote attackers to have unspecified impact via a large number of crafted requests.
CVE-2017-2684 1 Siemens 1 Simatic Logon 2025-04-20 N/A
Siemens SIMATIC Logon prior to V1.5 SP3 Update 2 could allow an attacker with knowledge of a valid user name, and physical or network access to the affected system, to bypass the application-level authentication.
CVE-2017-2682 1 Siemens 1 Ruggedcom Network Management Software 2025-04-20 N/A
The Siemens web application RUGGEDCOM NMS < V1.2 on port 8080/TCP and 8081/TCP could allow a remote attacker to perform a Cross-Site Request Forgery (CSRF) attack, potentially allowing an attacker to execute administrative operations, provided the targeted user has an active session and is induced to trigger a malicious request.
CVE-2017-14023 1 Siemens 2 Simatic Pcs7, Simatic Wincc 2025-04-20 4.9 Medium
An Improper Input Validation issue was discovered in Siemens SIMATIC PCS 7 V8.1 prior to V8.1 SP1 with WinCC V7.3 Upd 13, and V8.2 all versions. The improper input validation vulnerability has been identified, which may allow an authenticated remote attacker who is a member of the administrators group to crash services by sending specially crafted messages to the DCOM interface.
CVE-2017-12739 1 Siemens 2 Sm-2556, Sm-2556 Firmware 2025-04-20 N/A
An issue was discovered on Siemens SICAM RTUs SM-2556 COM Modules with the firmware variants ENOS00, ERAC00, ETA2, ETLS00, MODi00, and DNPi00. The integrated web server (port 80/tcp) of the affected devices could allow unauthenticated remote attackers to execute arbitrary code on the affected device.
CVE-2017-12738 1 Siemens 2 Sm-2556, Sm-2556 Firmware 2025-04-20 N/A
An issue was discovered on Siemens SICAM RTUs SM-2556 COM Modules with the firmware variants ENOS00, ERAC00, ETA2, ETLS00, MODi00, and DNPi00. The integrated web server (port 80/tcp) of the affected devices could allow Cross-Site Scripting (XSS) attacks if unsuspecting users are tricked into clicking on a malicious link.
CVE-2017-12735 1 Siemens 2 Logo\!, Logo\! 8 Bm Firmware 2025-04-20 7.4 High
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). An attacker who performs a Man-in-the-Middle attack between the LOGO! BM and other devices could potentially decrypt and modify network traffic.
CVE-2017-12740 1 Siemens 1 Logo\! Soft Comfort 2025-04-20 N/A
Siemens LOGO! Soft Comfort (All versions before V8.2) lacks integrity verification of software packages downloaded via an unprotected communication channel. This could allow a remote attacker to manipulate the software package while performing a Man-in-the-Middle (MitM) attack.
CVE-2021-37185 1 Siemens 95 Simatic Drive Controller Cpu 1504d Tf, Simatic Drive Controller Cpu 1504d Tf Firmware, Simatic Drive Controller Cpu 1507d Tf and 92 more 2025-04-18 7.5 High
A vulnerability has been identified in SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packets over port 102/tcp. A restart of the affected device is needed to restore normal operations.
CVE-2021-37204 1 Siemens 95 Simatic Drive Controller Cpu 1504d Tf, Simatic Drive Controller Cpu 1504d Tf Firmware, Simatic Drive Controller Cpu 1507d Tf and 92 more 2025-04-18 7.5 High
A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 Ready4Linux (All versions), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packet over port 102/tcp. A restart of the affected device is needed to restore normal operations.
CVE-2021-37205 1 Siemens 95 Simatic Drive Controller Cpu 1504d Tf, Simatic Drive Controller Cpu 1504d Tf Firmware, Simatic Drive Controller Cpu 1507d Tf and 92 more 2025-04-18 7.5 High
A vulnerability has been identified in SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packets over port 102/tcp. A restart of the affected device is needed to restore normal operations.
CVE-2023-51439 1 Siemens 2 Jt2go, Teamcenter Visualization 2025-04-17 7.8 High
A vulnerability has been identified in JT2Go (All versions < V14.3.0.6), Teamcenter Visualization V13.3 (All versions < V13.3.0.13), Teamcenter Visualization V14.1 (All versions < V14.1.0.12), Teamcenter Visualization V14.2 (All versions < V14.2.0.9), Teamcenter Visualization V14.3 (All versions < V14.3.0.6). The affected applications contain an out of bounds read past the end of an allocated structure while parsing specially crafted CGM files. This could allow an attacker to execute code in the context of the current process.
CVE-2022-2069 1 Siemens 2 Jt2go, Teamcenter Visualization 2025-04-16 7.8 High
The APDFL.dll in Siemens JT2Go prior to V13.3.0.5 and Siemens Teamcenter Visualization prior to V14.0.0.2 contains an out of bounds write past the fixed-length heap-based buffer while parsing specially crafted PDF files. This could allow an attacker to execute code in the context of the current process.
CVE-2014-4682 1 Siemens 2 Simatic Pcs7, Wincc 2025-04-12 N/A
The WebNavigator server in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows remote attackers to obtain sensitive information via an HTTP request.
CVE-2014-4683 1 Siemens 2 Simatic Pcs7, Wincc 2025-04-12 N/A
The WebNavigator server in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows remote authenticated users to gain privileges via a (1) HTTP or (2) HTTPS request.
CVE-2014-2254 1 Siemens 6 Simatic S7 Cpu-1211c, Simatic S7 Cpu 1200 Firmware, Simatic S7 Cpu 1212c and 3 more 2025-04-12 N/A
Siemens SIMATIC S7-1200 CPU PLC devices with firmware before 4.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted HTTP packets, a different vulnerability than CVE-2014-2255.
CVE-2016-9160 1 Siemens 2 Simatic Pcs 7, Simatic Wincc 2025-04-12 N/A
A vulnerability in SIEMENS SIMATIC WinCC (All versions < SIMATIC WinCC V7.2) and SIEMENS SIMATIC PCS 7 (All versions < SIMATIC PCS 7 V8.0 SP1) could allow a remote attacker to crash an ActiveX component or leak parts of the application memory if a user is tricked into clicking on a malicious link under certain conditions.
CVE-2014-2732 1 Siemens 1 Sinema Server 2025-04-12 N/A
Multiple directory traversal vulnerabilities in the integrated web server in Siemens SINEMA Server before 12 SP1 allow remote attackers to access arbitrary files via HTTP traffic to port (1) 4999 or (2) 80.
CVE-2016-4785 1 Siemens 9 Siprotec 4 En100, Siprotec Compact Model, Siprotec Compact Model 7rw80 and 6 more 2025-04-12 N/A
A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. The integrated web server (port 80/tcp) of the affected devices could allow remote attackers to obtain a limited amount of device memory content if network access was obtained. This vulnerability only affects EN100 Ethernet module included in SIPROTEC4 and SIPROTEC Compact devices.